Dehumidification
The highly efficient Ultra-Aire 100V dehumidifier utilizes refrigeration
to cool the incoming air stream below its dew point. This cooled and
drier air is used to pre-cool the incoming air stream resulting in a
significant increase in overall efficiency. After the pre-cooling stage,
the processed air is reheated by passing through the condenser coil.
The heat removed by the evaporator coil is returned to the air stream,
resulting in an overall temperature increase of the air leaving the unit.
The Ultra-Aire 100V is controlled by 24 volt remote wired controls. A
variety of controls are available suitable to various applications.
Fresh Air Ventilation
Optional fresh outdoor air may be ducted to the unit via a six inch
round duct. This provides fresh air to dilute pollutants and maintain
high oxygen content in the air. The amount of fresh air ventilation can
be regulated by a variety of dampers and controls.
Air Filtration
The UA-100V includes air filtration to improve indoor air quality. A
MERV-11 media filter is standard. An optional MERV-14 deep pleated
95% media filter is available for optimum air filtration and to reduce
potentially harmful airborne particles. If the optional filter is chosen,
the standard filter operates as a prefilter.
© 2008 Therma-Stor LLC
Manual P/N TS-200L
P.O. Box 8680 Madison, WI 53708
TOLL-FREE 1-800-533-7533
www.thermastor.com
sales@thermastor.com
INSTALLER’S & OWNER’S MANUAL
HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER
P/N 4022200 • Serial No.________________________ Install Date:___________
Sold by:
Page view 0
1 2 3 4 5 6 ... 20 21

Summary of Contents

Page 1 - Air Filtration

DehumidificationThe highly efficient Ultra-Aire 100V dehumidifier utilizes refrigeration to cool the incoming air stream below its dew point. This cooled

Page 2 - TABLE OF CONTENTS

10Ultra-Aire 100V Installer’s & Owner’s ManualFOR HVAC INSTALLER AND HOMEOWNER6. Maintenance6.1 Standard Air FilterThe Ultra-Aire is equipped with

Page 3 - SAFETY PRECAUTIONS

No dehumidification, compressor does not run but fan runs with fan switch and ventilation timer OFF and humidity control turned to ON.1. Defective com

Page 4 - FOR HVAC INSTALLER ONLY

6. Compressor terminal C and overload terminal 1: No continuity indicates a defective overload lead.7. Overload terminals 1 and 3: If there is n

Page 5

Ultra-Aire does not run, try turning the humidity control clockwise until it reaches the stop and the knob pointer points at “ON”.The Ultra-Aire is eq

Page 6

ULTRA-AIR 100V ELECTRICAL SCHEMATIC14Ultra-Aire 100V Installer’s & Owner’s Manual

Page 7

ULTRA-AIRE 100V PICTORIAL ELECTRICAL DIAGRAM15Ultra-Aire 100V Installer’s & Owner’s Manual

Page 8 - ATTENTION INSTALLER

ULTRA-AIRE 100V SERVICE PARTS LISTItem Part No. QTY. Description1 4022254 1 Accumulator2 4021475 1 Air Filter, Pleated Cloth3 4026930 1 Fa

Page 9 - DEH 3000/DEH 3000

ULTRA-AIRE 100V OPTIONAL PARTS LISTItem Part No. QTY. Description26 4022489 1 Air Filter, High Efficiency, Pleated Microglass Paper, 90%-95%27 4

Page 10 - 7.3 Troubleshooting

ULTRA-AIRE 100V EXTERNAL INSULATION KIT18Ultra-Aire 100V Installer’s & Owner’s Manual

Page 11 - 7.4 Refrigerant Charging

ULTRA-AIRE 100V CONTROL PANEL INSTALLATION1. The following installation instructions are for both new construction and retrofit applications. For ne

Page 12 - 7.7A Humidity Control

Table of ContentsSafety Precautions ... 21. Intended Application ...

Page 13 - 7.8 Defrost Thermostat

20 Ultra-Aire 100V Installer’s & Owner’s ManualLimited WarrantyLimited Warranty. Therma-Stor, LLC (“Therma-Stor”) warrants as follows: (i) the Sa

Page 14

PO Box 8680 • Madison, WI 53708 Phone: 608-222-5301 • Fax: 608-222-1447 Web: www.thermastor.com • Email: [email protected] in this docum

Page 15

3. Installation3.1 LocationThe Ultra-Aire should be located near the existing air handling system to minimize the required ductwork for connecting the

Page 16

Duct Sizing: For total duct lengths up to 25', use aminimum 8" diameter round or equivalent rectangular. For longer lengths, use a minimum 1

Page 17

crawlspace. Duct the other side of the tee to the air return of the existing HVAC system. If the existing HVAC system has a central return, duct the o

Page 18

4.3 Humidity Control AdjustmentSet the humidity control to the desired humidity level for the home. The dehumidifier will run continuously until the re

Page 19

to the right of the time will indicate if the ventilation timer is on or off. The I/O button will manually override scheduled programs if the timer is

Page 20 - Limited Warranty

8Ultra-Aire 100V Installer’s & Owner’s ManualATTENTION INSTALLERWIRE THE UNIT AND CONTROL PACKAGE AS SHOWN IN THE DIAGRAM BELOWWARNING: DO NOT all

Page 21

9Ultra-Aire 100V Installer’s & Owner’s Manual5. Optional Dehumidifier & Ventilation System ControllerWhen used with Ultra-Aire Whole House Ven